Level 2 Power networks

Modelling the elements of a network, calculating the power flow (load flow) and the short-circuit currents.
Tutorial Version 2.0.0 November 2026 EN / FR Click for the French version
Level 2 — Power networks
NRJXpert 2.0.0 · November 2026

📘Introduction

Objectives

  • Establish the equivalent circuit of a line, a cable and a transformer from manufacturer data.
  • Convert physical quantities to per-unit quantities and back.
  • Calculate a voltage drop and losses; check a voltage profile.
  • Write the load-flow equations, do one Gauss-Seidel iteration by hand and interpret the convergence of the three methods.
  • Calculate three-phase, phase-to-phase and phase-to-earth short-circuit currents according to IEC 60909 and deduce the breaking capacity.

Prerequisites: level 1, elementary matrix calculus. Duration: 20 to 25 h.

↑ Back to top

🧵2.1 Lines and cables

A line or cable is characterised by four per-length quantities (per km): resistance r, inductance l (reactance x = lω), capacitance c and conductance g (neglected). Orders of magnitude:

Assetr (Ω/km)x (Ω/km)c (nF/km)Remark
MV overhead line, AAAC 148 mm²0.22 to 0.270.35 to 0.409 to 10R/X ≈ 0.7
MV overhead line, AAAC 54.6 mm²0.600.409R/X ≈ 1.5
MV underground cable, Al 150 mm²0.210.11250 to 400large capacitance
LV copper cable 4 × 95 mm²0.240.08—R/X ≈ 3

Models according to the electrical length: short line (< 80 km overhead): R + jX in series; medium line (π model): R + jX in series and C/2 to earth at each end; long line: distributed-parameter model. NRJXpert offers the R, L, RL and RLC π models (Network palette) with R = r·ℓ, L = l·ℓ, C = c·ℓ.

Zero-sequence quantities. For earth faults, r₀, x₀ (return through the earth, about 3 times x for overhead lines) and c₀ are also needed: « Zero sequence » section of the lines.

↑ Back to top

🔸2.2 Transformers

The Kapp equivalent circuit reduces the transformer to a series impedance Zsc = Rsc + jXsc and a magnetising branch (Rfe ∥ jXm), from the short-circuit test (usc, Psc) and the no-load test (i₀, P₀):

Zsc = usc·U²/Sn    Rsc = Psc·U²/Sn²    Xsc = √(Zsc² − Rsc²)    (U = voltage of the side to which the impedance is referred)

The vector group (Dyn, YNd, Yyn…) plays no role in the positive sequence but determines the zero-sequence path: a delta winding blocks the zero-sequence current, an earthed star neutral lets it through. Dyn11, very common in distribution, isolates the MV network from LV earth faults and provides the LV network with an earthed neutral.

Example 2.1 — Distribution transformer

250 kVA, 30 kV / 400 V, usc = 4 %, Psc = 3.25 kW. Calculate Zsc, Rsc, Xsc referred to the secondary, the rated current and the voltage drop at full load with cos φ = 0.8.

Show the solution

Zsc = 0.04 × 400²/250 000 = 25.6 mΩ; Rsc = 3 250 × 400²/250 000² = 8.32 mΩ; Xsc = 24.21 mΩ. In = 250 000/(√3 × 400) = 360.8 A.

ΔU ≈ √3·I·(R cos φ + X sin φ) = √3 × 360.8 × (0.00832 × 0.8 + 0.02421 × 0.6) = 13.2 V, i.e. 3.3 %.

These are exactly the values computed by the parameter dialog of the NRJXpert three-phase transformer (Network palette).

↑ Back to top

📗2.3 Per-unit system

A base power Sb (common to the whole network, e.g. 100 MVA or 10 MVA) and a base voltage Ub per voltage level (transformer ratios) are chosen. Every quantity is divided by its base:

Zb = Ub²/Sb    Ib = Sb/(√3·Ub)    zpu = Z/Zb    change of base: z₂ = z₁·(Sb2/Sb1)·(Ub1/Ub2)²

Advantages: transformers disappear (ratio 1 in pu), voltages are close to 1 pu, orders of magnitude can be compared between networks (the usc of a transformer = its impedance in pu on its own base). The NRJXpert server works in pu for the load flow (Sb = 100 MVA, Ub = network voltage entered in the calculation settings).

↑ Back to top

📉2.4 Voltage drop and losses

For a line of impedance R + jX carrying P + jQ at line voltage U:

ΔU/U ≈ (R·P + X·Q)/U²    losses: ΔP = R·(P² + Q²)/U² = 3·R·I²

Practical consequences: the voltage drop depends mainly on P in resistive networks (LV, MV with small cross-sections) and on Q in inductive networks (HV); hence voltage control through reactive power in transmission, and the role of controlled inverters in distribution (level 5). Losses vary as the square of the power and the inverse square of the voltage: doubling the voltage divides losses by 4.

Example 2.2 — MV feeder

A 10 km, 20 kV line (r = 0.3 Ω/km, x = 0.35 Ω/km) supplies 2 MW at cos φ = 0.9 at its end. Voltage drop and losses?

Show the solution

R = 3 Ω, X = 3.5 Ω, Q = 2 × tan(25.84°) = 0.969 Mvar. ΔU/U = (3 × 2 + 3.5 × 0.969)/20² = 2.35 % (470 V); losses = 3 × (2² + 0.969²)/20² = 0.037 MW = 37 kW (1.9 %).

↑ Back to top

🔀2.5 Load flow: formulation

The load flow (power flow) calculates the steady state of a network from the generated and consumed powers. Since powers rather than impedances are imposed, the equations are non-linear.

Bus types

TypeDataUnknownsIn NRJXpert
Slack (swing)|V|, θ = 0P, Q« Slack » generator: the source substation, which covers the losses
Generation (PV)P, |V|Q, θVoltage-controlled generator
Load (PQ)P, Q|V|, θLoad bus

Admittance matrix and equations

Ybus is built element by element: for a branch of admittance yik between i and k, yik is added to Yii and Ykk and subtracted from Yik and Yki; admittances to earth (C/2 of the lines) are added to the diagonal. At node i:

Si* = Pi − jQi = Vi*·Σk YikVk
Pi = Σk |Vi||Vk||Yik| cos(θik − δi + δk)    Qi = −Σk |Vi||Vk||Yik| sin(θik − δi + δk)
↑ Back to top

📘2.6 Solution methods

Gauss-Seidel

Vi(n+1) = [ (Pi − jQi)/Vi(n)* − Σk≠i YikVk ] / Yii

For each node the most recent voltages are used. PV node: Qi is first calculated with the current voltages, then |Vi| is reset to its set-point after the update. Simple, but slow convergence (tens of iterations); an acceleration factor (1.4 to 1.6) helps.

Example 2.3 — One iteration by hand

Two-node network in pu: node 1 slack V₁ = 1∠0°; line z = 0.02 + j0.06; node 2 load 0.8 + j0.4 pu. Start from V₂ = 1∠0° and iterate down to 10⁻⁴.

Show the solution

y = 1/z = 5 − j15; Y₂₂ = 5 − j15, Y₂₁ = −5 + j15. S₂ = −0.8 − j0.4 (load = negative injection).

V₂(1) = [(−0.8 + j0.4)/1 + (5 − j15)·1]/(5 − j15) = 1 + (−0.8 + j0.4)/(5 − j15) = 1 − 0.04 − j0.04 = 0.96 − j0.04 → 0.9608∠−2.39°.

Then: 0.9575∠−2.39°; 0.95736∠−2.395°; 0.95735∠−2.395° (difference < 10⁻⁴ at the 4th iteration). The final voltage is 0.9573 pu ∠−2.39°.

Newton-Raphson

The power equations are linearised around the current state and solved for the corrections:

[ ΔP ; ΔQ ] = [ ∂P/∂δ   ∂P/∂|V| ; ∂Q/∂δ   ∂Q/∂|V| ] · [ Δδ ; Δ|V| ]    (Jacobian J, recalculated at each iteration)

Quadratic convergence: 3 to 6 iterations whatever the size of the network, but each iteration costs a factorisation of the Jacobian. It is the reference method.

Fast decoupled (Stott)

Assumptions: R ≪ X, small angles, |V| ≈ 1. Then ∂P/∂|V| ≈ 0 and ∂Q/∂δ ≈ 0, and the sub-matrices become constant (B' and B''): they are factorised only once. Very fast on transmission networks, but slow or divergent when R/X is large (distribution networks): see the lab below and the distribution load flow of level 5.

Lab 3 — Load flow of a three-node 30 kV network

Data (Un = 30 kV, AAAC lines, r = 0.27 Ω/km, x = 0.38 Ω/km):

ElementData
P1 — source substation (slack)V = 31.5 kV, phase 0
G2 — power plant (PV bus)Pgen = 3 MW, V = 31.4 kV
Ch3 — load (PQ bus)Pload = 5 MW, Qload = 2.5 Mvar
LinesL12 = 15 km (4.05 + j5.70 Ω), L13 = 20 km (5.40 + j7.60 Ω), L23 = 10 km (2.70 + j3.80 Ω)
  1. Calculation settings: network voltage 30 kV, frequency 50 Hz.
  2. Network (load flow) palette, single-line variant: place two generators and a load bus; set P1 as slack, G2 as PV bus, Ch3 as PQ load with the values above (voltages in kV, powers in MW and Mvar).
  3. Connect the three nodes with three impedances (Passive elements section) of the R + jX values above, or with three RL lines from the palette (length and per-length characteristics; l = 0.38/314.16 = 1.21 mH/km).
  4. Calculation Load flow, method Newton-Raphson, F5.
  5. Compare with the results below (exemples/loadflow_30kV_3noeuds.xml can also be opened with Help › Open a tutorial example: the « Calculate a network file (XML) » window sends this network to the server):
NodeV (kV)AnglePgen (MW)Qgen (Mvar)
P131.5000°2.0601.429
G231.400+0.006°3.0001.156
Ch330.937−0.476°——

Currents: L12 = 8.3 A, L13 = 38.4 A, L23 = 66.0 A; load current 104.3 A. Losses = 2.060 + 3.000 − 5.000 = 60 kW (check: Σ 3·R·I² = 0.8 + 23.9 + 35.3 kW).

To do: run again with Gauss-Seidel (20 iterations) then Fast decoupled (35 iterations) against 3 for Newton-Raphson. Why is fast decoupled the slowest here? (R/X = 0.71: the assumption R ≪ X does not hold.) Set G2 to 30.5 kV: G2 then absorbs 6 Mvar. Conclusion: in a meshed network, small voltage set-point differences cause large reactive power flows.

↑ Back to top

⚡2.7 Short circuit according to IEC 60909-0

Principle: equivalent voltage source

All sources are replaced by a single source c·Un/√3 at the fault point; loads are neglected (except motors) and the network is reduced to the impedance seen from the fault. The voltage factor c covers voltage variations and approximations:

Nominal voltagecmax (breaking capacity, withstand)cmin (protection settings)
Un ≤ 1 kV, tolerance +6 %1.050.95
Un ≤ 1 kV, tolerance +10 %1.100.95
Un > 1 kV1.101.00

Symmetrical components

An unbalanced three-phase system is decomposed (Fortescue) into three balanced systems: positive (1), negative (2) and zero (0) sequence, with a = ej2π/3:

[Va ; Vb ; Vc] = [1 1 1 ; 1 a² a ; 1 a a²]·[V₀ ; V₁ ; V₂]

Each element has three impedances Z₁, Z₂, Z₀ (static elements: Z₂ = Z₁); the impedance seen from the fault is calculated in each of the three networks, which are then combined according to the type of fault:

FaultInitial symmetrical current I"kCombination of the networks
Three-phasec·Un / (√3·|Z₁|)positive sequence only
Phase-to-phasec·Un / |Z₁ + Z₂|positive and negative in opposition
Two-phase-to-earthearth current I"kE2E = √3·c·Un·|Z₂| / |Z₁Z₂ + Z₁Z₀ + Z₂Z₀|negative ∥ zero
Phase-to-earth√3·c·Un / |Z₁ + Z₂ + Z₀|all three in series

Peak current: ip = κ·√2·I"k with κ = 1.02 + 0.98·e−3R/X. Fault far from generators: breaking current Ib and steady-state current Ik equal to I"k. Short-circuit power: S"k = √3·Un·I"k.

Example 2.4 — Faults at the end of a 20 kV feeder

The upstream network is represented at the substation by Z₁ = Z₂ = 0.1 + j2 Ω and Z₀ = 0.05 + j1 Ω (earthed neutral). A 10 km line has r = 0.3, x = 0.35, r₀ = 0.45, x₀ = 1.2 Ω/km. Calculate I"k at the end of the line for the four types of fault (maximum Isc).

Show the solution

Z₁ = Z₂ = 0.1 + 3 + j(2 + 3.5) = 3.1 + j5.5 Ω (|Z₁| = 6.314 Ω); Z₀ = 0.05 + 4.5 + j(1 + 12) = 4.55 + j13 Ω; c = 1.1.

FaultCalculationI"k
Three-phase1.1 × 20 000/(√3 × 6.314)2 012 A
Phase-to-phase22 000/|6.2 + j11|1 742 A
Two-phase-to-earthlargest phase current1 907 A
Phase-to-earth√3 × 22 000/|10.75 + j24|1 449 A

κ = 1.02 + 0.98·e−3 × 0.5636 = 1.201; ip = 1.201 × √2 × 2 012 = 3.42 kA; S"k = 69.7 MVA. Note: the phase-to-earth fault is the weakest here because Z₀ > Z₁; near a Dyn transformer with an earthed neutral, it is often the opposite.

Lab 4 — Short circuit in NRJXpert

  1. Calculation settings: network voltage 20 kV.
  2. Place a generator (single-line variant); Short-circuit column: Rd = 0.1, Xd = 2 Ω, Ri = Xi = 0 (Z₂ = Z₁), earthed neutral, R0 = 0.05, X0 = 1 Ω.
  3. Place an RL line (Network palette): 10 km, r = 300 mΩ/km, l = 1.114 mH/km (0.35 Ω/km at 50 Hz); Zero sequence section: r0 = 0.45, x0 = 1.2 Ω/km. Place a load bus at the end (it is neglected in the calculation) and connect.
  4. Double-click on the terminal at the end of the line: three-phase Fault, maximum current, Un = 20 kV. Choose the Short circuit calculation and run.
  5. Read the summary (I"k, ip, κ, S"k, Z1, Z2, Z0, I"k of the four types) and compare with example 2.4. Repeat with a phase-to-earth fault: earth current 1 449 A (file exemples/courtcircuit_20kV_monophase.xml).
  6. Right-click on the line › Short circuit at this point…: plot I"k against the distance (0, 2, 4, …, 10 km). Why is the curve not in 1/d?
↑ Back to top

⚡2.8 Protection: what short-circuit currents are used for

  • Breaking capacity of the device ≥ maximum I"k (and ip ≤ making capacity) at the point of installation.
  • Sensitivity: the minimum short-circuit current (cmin, furthest fault, often phase-to-earth or phase-to-phase) must trip the protection within the required time: this is the « minimum Isc » calculation of NRJXpert.
  • Thermal withstand of cables: I²·t ≤ k²·S² (k ≈ 143 for XLPE-insulated copper).
  • Selectivity: only the protection immediately upstream of the fault must trip (current, time or logic selectivity).
  • Inverters: their contribution is limited to 1.1 to 1.5 times their rated current; a network supplied mainly by inverters has low fault currents, which makes detection harder (level 5).
↑ Back to top

🎯Exercises

Exercise 1 — Short circuit at the secondary of a transformer

The transformer of example 2.1 is supplied by a network of infinite short-circuit power. Calculate the three-phase I"k at the secondary (c = 1.05), κ and ip.

Show the solution

I"k = 1.05 × 400/(√3 × 0.0256) = 9.47 kA; R/X = 0.344; κ = 1.02 + 0.98·e−1.031 = 1.370; ip = 1.370 × √2 × 9.47 = 18.3 kA. The LV main breaker must have a breaking capacity of at least 10 kA (15 or 25 kA is chosen to account for the actual short-circuit power of the upstream network).

Exercise 2 — Change of base

A 2 MVA, 30/0.4 kV transformer has usc = 6 %. Express its impedance in pu on a 100 MVA base, then in ohms on the 30 kV side.

Show the solution

z = 0.06 × 100/2 = 3 pu; Zb = 30²/100 = 9 Ω; Z = 27 Ω (= 0.06 × 30²/2).

Exercise 3 — Voltage profile

In lab 3, the load becomes 8 MW, 4 Mvar. Without detailed calculation, what will happen to V3, to Qgen of G2 and to the losses? Check with NRJXpert.

Show the solution

Forecast: V3 decreases (≈ (R·P + X·Q)/U² increases); G2, which holds its voltage, supplies more reactive power; losses grow roughly as the square of the flows. Calculation (Newton-Raphson, 3 iterations): V3 = 30.629 kV (−1.23°) instead of 30.937 kV; Qgen of G2 = 3.71 Mvar instead of 1.16; the substation supplies 5.17 MW and 0.53 Mvar; losses = 5.172 + 3 − 8 = 172 kW, i.e. 2.9 times more for a load 1.6 times larger.

Exercise 4 — Iterative methods

Explain why Newton-Raphson converges in 3 iterations from any reasonable initialisation (« flat » voltages 1∠0°), while Gauss-Seidel needs 20. What happens if the load becomes too large (beyond the maximum transmissible power)?

Show the solution

NR uses the derivatives (tangent): near the solution the error is squared at each iteration. GS corrects each node separately, with linear convergence. Beyond the voltage collapse point (nose of the P-V curve) there is no solution any more: no method converges and the server returns a non-convergence message.

↑ Back to top

📋Level 2 quiz

1. In the π model of a line, the total capacitance C is distributed:

  1. entirely at the sending end
  2. C/2 at each end
  3. in series with R
  4. C at each end
C/2 on each side: this is what NRJXpert does (corrected in October 2026: each side used to be C·l).

2. A transformer has usc = 4 %. Its impedance on its own base is:

  1. 4 Ω
  2. 0.4 pu
  3. 0.04 pu
  4. 25 pu
usc is the impedance in pu on the base (Sn, Un).

3. On a highly resistive low-voltage network, the voltage drop depends mainly on:

  1. the active power
  2. the reactive power
  3. the frequency
  4. the cable capacitance
ΔU/U ≈ (RP + XQ)/U² with R ≫ X.

4. In a load flow, the unknowns of a PV node are:

  1. P and Q
  2. |V| and θ
  3. P and θ
  4. Q and θ
P and |V| are imposed; Q and the angle are calculated.

5. The slack node is used to:

  1. set the frequency
  2. provide the angle reference and cover the unknown losses
  3. represent the loads
  4. control the reactive power of the PV nodes
Since losses are known only after the calculation, one node must balance the power.

6. The fast decoupled method is poorly suited to:

  1. large transmission networks
  2. meshed networks
  3. distribution networks with high R/X
  4. networks without a PV node
It assumes R ≪ X; in distribution the backward/forward sweep is preferred (level 5).

7. To size the breaking capacity of a circuit breaker, one uses:

  1. the maximum I"k (cmax)
  2. the minimum I"k (cmin)
  3. the rated current
  4. the overload current
The minimum current is used for the setting (sensitivity) of the protection.

8. A phase-to-earth fault connects the sequence networks:

  1. positive only
  2. positive and negative in opposition
  3. negative and zero in parallel
  4. positive, negative and zero in series
I"k1 = √3·c·Un/|Z1 + Z2 + Z0|.

9. A delta winding:

  1. lets zero-sequence current through to the upstream network
  2. blocks the zero-sequence current
  3. doubles the positive-sequence impedance
  4. suppresses the three-phase fault current
The zero-sequence current circulates in the delta without leaving on the lines.

10. For R/X = 0.1, the factor κ is about:

  1. 1.02
  2. 1.30
  3. 1.75
  4. 2.00
κ = 1.02 + 0.98·e−0.3 = 1.746: highly inductive network, large DC component.
↑ Back to top