Appendices: formulas and tables

Tutorial Version 2.0.0 November 2026 EN / FR Click for the French version
Appendices: formulas and tables
NRJXpert 2.0.0 · November 2026

📐A.1 Formula sheet

Circuits

U = Z·I   S = U·I* = P + jQ   ZL = jLω   ZC = 1/(jCω)   ω = 2πf
Three-phase: U = √3·V   P = √3·U·I·cos φ   QC = P(tan φ₁ − tan φ₂)   C = QC/(ωU²)

Networks

Zb = Ub²/Sb   Ib = Sb/(√3Ub)   ΔU/U ≈ (RP + XQ)/U²   ΔP = R(P² + Q²)/U²
Transformer: Zsc = uscU²/Sn   Rsc = PscU²/Sn²   Xsc = √(Zsc² − Rsc²)
Load flow: Si* = Vi*ΣkYikVk   Gauss-Seidel: Vi = [(Pi − jQi)/Vi* − Σk≠iYikVk]/Yii

Short circuit (IEC 60909-0)

I"k3 = cUn/(√3|Z₁|)   I"k2 = cUn/|Z₁ + Z₂|   I"k1 = √3cUn/|Z₁ + Z₂ + Z₀|
I"kE2E = √3cUn|Z₂|/|Z₁Z₂ + Z₁Z₀ + Z₂Z₀|   ip = κ√2 I"k   κ = 1.02 + 0.98e−3R/X   S"k = √3UnI"k

Solar

δ = 23.45 sin(360(284 + n)/365)   ωs = arccos(−tan φ tan δ)   Kt = H/H₀
Hβ = H[(1 − Hd/H)Rb + (Hd/H)(1 + cos β)/2 + ρ(1 − cos β)/2]
P = Pp(G/1000)(1 + γ(Tc − 25))   Tc = Ta + (NOCT − 20)G/800   E = Pp·Hβ·PR

Stand-alone PV (NRJXpert method)

Qd = Ed/(U·ηconv·0.98·0.9)   C = Qd·autonomy(h)/24   Np,batt = ⌈C/(Cbatt·DoD)⌉
PWM: Np = ⌈Qd/(0.9·H·Imp)⌉   MPPT: Pp = QdU/(H·0.9·fT·0.96)   charge controller and inverter: × 1.25

Wiring

Ib = 1.25·I   In ≥ Ib   Iz0(S)·kθ·kg ≥ In   kθ = √((90 − θa)/60)
ΔU = b(ρL/S cos φ + λL sin φ)I   (b = 2 DC and single-phase, 1 three-phase on V)   ρCu = 0.0225   ρAl = 0.036 Ω·mm²/m   λ = 0.08 mΩ/m

Wind

P = ½ρAv³   f(v) = (k/c)(v/c)k−1e−(v/c)k   v̄ = cΓ(1 + 1/k)   ½ρc³Γ(1 + 3/k)
v(H) = v(Hmeas)ln(H/z₀)/ln(Hmeas/z₀)   E = 8 760∫P(v)f(v)dv(1 − losses)   CF = E/(8 760Pn)

Solar water pumping

TDH = HG + PC   Eel = 2.725·V·TDH/(ηpηmηconv)   Pc = Eel/(Ens·ηc)
Qmax = πV/(2ΔT)   PH = Qmax·TDH/367   Pc = PH/(ηpηmηconvηc)·1 000/G   (V in m³/d, Q in m³/h, PH in kW)

Economics

CRF = a(1 + a)N/((1 + a)N − 1)   NPV = ΣFn/(1 + a)n   LCOE = Cdisc/ΣEn/(1 + a)n
real rate = (1 + a)/(1 + i) − 1   minimum subsidy = max(0, −NPV/I₀)

Smart grids (levels 6 and 7)

SAIDI = Σ(Ni·ti)/NT   SAIFI = ΣNi/NT   CVRf ≈ 2Z + I   RoCoF ≈ ΔP·f₀/(2H·ΣSn)
NTL = Einjected − Emetered − Etechnical   precision = TP/(TP + FP)   recall = TP/(TP + FN)   frame success = 1 − (1 − pⁿ)^(r+1)
↑ Back to top

🧵A.2 Wiring tables (copper, XLPE insulation, installation method C, 30 °C)

Cross-section (mm²)1.52.54610162535507095120150185240300
Iz0, 2 loaded conductors (A)2433455880107138171209269328382441506599693
Iz0, 3 loaded conductors (A)223040527196119147179229278322371424500576

Source: IEC 60364-5-52, table B.52.5 (values used by NRJXpert). Aluminium: about 78 % of these values, from 16 mm².

Ambient temperature (°C)2530354045505560
kθ (XLPE insulation, 90 °C)1.041.000.960.910.870.820.760.71
Bunched circuits123469
Grouping factor kg (indicative)1.000.800.700.650.570.50

Standard ratings (A): 2, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1 000, 1 250, 1 600.

↑ Back to top

⚡A.3 Short circuit: factor c and coefficient κ

Nominal voltagecmaxcmin
≤ 1 kV (tolerance +6 %)1.050.95
≤ 1 kV (tolerance +10 %)1.100.95
> 1 kV1.101.00
R/X00.10.20.30.50.71.0
κ2.001.751.561.421.241.141.07
↑ Back to top

📗A.4 Orders of magnitude

QuantityTypical value
Irradiation in Senegal4.3 (December) to 6.7 (April) kWh/m²/d on the horizontal plane in Dakar; ≈ 2 000 kWh/m²/yr
Grid-connected PV yield1 500 to 1 650 kWh/kWp/yr (PR 0.75 to 0.82)
Coastal wind at 10 m4 to 6 m/s on average (northern coast), lower inland
Solar pumpingrural demand 20 to 50 l/inh/d; pump × motor efficiency 30 to 50 %; tank of 1 to 3 days of consumption
Lifetimesmodules 25 years; lead-acid batteries 3 to 7 years, LFP 10 to 12 years; inverters 8 to 12 years; charge controllers 10 to 15 years; cables 25 years
Efficienciesinverter 92 to 97 %; MPPT 96 to 98 %; lead-acid battery 80 to 85 %, lithium 92 to 95 %
Genset consumption0.25 l/kWh at full load, 0.35 to 0.45 l/kWh at low load
Discount rate6 to 12 %; inflation 2 to 4 %
Non-technical lossesfrom 1 to more than 15 % of the energy supplied depending on the network; smart meter + installation ≈ 50 to 100 kF
↑ Back to top

⚙️A.5 Calculators

↑ Back to top

🧩A.6 Bibliography and standards

  • H. Saadat, Power System Analysis, McGraw-Hill — load flow, short circuit, symmetrical components.
  • J. J. Grainger, W. D. Stevenson, Power System Analysis, McGraw-Hill.
  • W. H. Kersting, Distribution System Modeling and Analysis, CRC Press — backward/forward sweep, unbalanced networks.
  • M. E. Baran, F. F. Wu, “Network reconfiguration in distribution systems for loss reduction and load balancing”, IEEE Trans. Power Delivery, 1989 — IEEE 33-bus network.
  • J. A. Duffie, W. A. Beckman, Solar Engineering of Thermal Processes, Wiley — solar geometry, tilted plane.
  • J. F. Manwell, J. G. McGowan, A. L. Rogers, Wind Energy Explained, Wiley — Weibull, power curves.
  • IEC 60909-0:2016 (short-circuit currents); IEC 60364 / NF C 15-100 (LV installations); UTE C15-712-1 (PV installations); IEC 61400-12-1 (wind turbine power curves); IEEE 1547-2018 (DER interconnection); IEEE 2030.7 / 2030.8 (microgrids); IEC 62056 (DLMS/COSEM); OpenADR 2.0b; IEC 62443 and IEC 62351 (cybersecurity).
↑ Back to top

👤Author

LT
Prof. Lamine THIAW
Department of Electrical Engineering
École Supérieure Polytechnique
Cheikh Anta Diop University, Dakar
lamine.thiaw@ucad.edu.sn
lamine.thiaw@esp.sn

November 2026