Teacher's guide

Using NRJXpert to train technicians and engineers: organisation, progressions, sessions, assessment.
Tutorial Version 2.0.0 November 2026 EN / FR Click for the French version
Teacher's guide
NRJXpert 2.0.0 · November 2026

📘1. Setting up the room

  • Client: Java 17 or later and JavaFX 21 (mvn clean javafx:run, or a packaged version).
  • Calculation server: hosted remotely (VPS); nothing to install on the computers. Enter on each computer (or give to the students) the institution's access key: Simulation › Calculation and server settings, « Encrypted connection » ticked. One key per institution, valid for the academic year; report to the supplier any key circulated outside the institution (it will be revoked and replaced). Before the session, check that the room has Internet access and that the institution's firewall lets the server port through (Test the connection from one computer: it must show « valid key »). A whole class calculating at the same time is not a problem: each calculation weighs a few kilobytes and takes less than one second (a few seconds for the DER studies of level 5, up to about fifteen seconds for the test bench of level 7).
  • Unstable connection: schedule the network sessions (levels 1, 2, 5, 6 and 7) at times when the connection is reliable; the photovoltaic, wind and economics sessions (levels 3 and 4) work offline. The reference results of the tutorial allow marking even without the server.
  • Examples: when the tutorial is first opened, they are copied to ~/.nrjxpert/aide/tutoriel/exemples/; a student who modifies them keeps his or her version.
  • Weather data: downloading them also requires the Internet; prepare the CSV files in advance for an offline session.
  • Language: with the interface in English (Options › Language), the Help menu opens the English pages of the tutorial.
↑ Back to top

👩‍🏫2. Progressions

ProgrammeVolumeContentAssessment
Higher technician diploma in electrical engineering, professional bachelor in renewable energy40 h (12 h lectures, 28 h labs) Level 1; level 3 § 3.1 to 3.4; level 4 § 4.1 to 4.3; case study 1 (decentralised part)2 marked labs + 1 sizing report
Bachelor in electrical engineering (3rd year)60 hLevels 1 and 2; level 3 complete; level 4Written exam + marked labs
Engineering school / master (1st year)60 hLevel 2 in depth (load flow, short circuit); levels 3 and 4; case studies 1 to 3Project in pairs + exam
Master in renewable energy / power networks (2nd year)40 hLevel 5; case studies 2 and 4; projects A to C of level 5Project + presentation
Smart grid specialisation (2nd-year master, specialised master, utility engineers)30 h + projectLevel 6 complete: SGAM, FLISR and reliability, IVVC/r, VPP, microgrids, EV, CIM and IEC 61850, owner's engineering; synthesis projectOwner's engineering mission report + presentation
Smart grid expert (after the specialisation)24 to 30 h + assignmentLevel 7: IEEE 2030.8 tests, smart metering and non-technical losses, DLMS/COSEM data collection, OpenADR 2.0b demand response, IEC 62443 cybersecurity; expert assignment § 7.6Test report + loss audit + risk assessment, presentation
Continuing education for smart grid consultants / project managers3 daysLevel 6 § 6.1, 6.2, 6.8, 6.9, 6.10; labs 6.3 and 6.9; use case sheets on a real projectUse case sheet + bid analysis grid
Continuing education (consulting firms, installers)3 to 5 daysLevel 3, wiring, level 4, case study adapted to the tradeReal case study
↑ Back to top

👩‍🏫3. Lab sessions

SessionDurationContent (references to the tutorial)Deliverable
1. Getting started2 hLab 1 (load and RL line), examples 1.1 and 1.2 drawnTable hand calculation / software
2. Three-phase and compensation3 hLab 2, example 1.4, exercise 3 of level 1Report
3. Transformer and voltage drop3 hExamples 2.1 and 2.2; three-phase transformer of the paletteReport
4. Load flow4 hExample 2.3 by hand, lab 3, exercise 3 of level 2Comparison of the 3 methods, voltage profile
5. Short circuit4 hExample 2.4, lab 4, exercise 1 of level 2, case study 3Choice of the protections
6. Solar resource and weather2 hLab 5, example 3.1Site sheet
7. Stand-alone PV system4 hExample 3.3, lab 6, exercise 1 of level 3Sizing report
8. Wiring and costs3 hExample 3.4, lab 7, exercise 2 of level 3Table of links, quotation
9. Wind3 hExamples 3.6 and 3.7, lab 8, case study 4Production note
10. Solar water pumping2 hExample 3.8, lab 8 bis, exercise 4 of level 3, case study 5Pump and array sizing note
11. Economics and viability4 hExamples 4.1 to 4.4, lab 9, case study 2NPV, IRR, LCOE, sensitivity

For level 5, plan 3 sessions of 4 h (lab 10 and projects A to C).

For level 6, plan 5 sessions of 4 h: (1) SGAM and protocols (tools 6.1 and 6.8, lab 6.1); (2) FLISR and reliability (example 6.3, lab 6.3, reliability calculator); (3) IVVC/r and CVR (example 6.4); (4) VPP, EV and microgrids (examples 6.5 and 6.6, lab 6.7); (5) owner's engineering: IEC 62559 sheet, specification, TCO, acceptance plan (lab 6.9). The interactive tools (SGAM mapping, use case sheet, self-assessment) keep the entries in the student's browser: have the work exported (Markdown or text) to hand it in.

For level 7, plan 4 sessions of 4 h and the assignment: (1) microgrid test bench (example 7.1, lab 7.1); (2) smart metering and losses (examples 7.2, labs 7.2); (3) OpenADR demand response (example 7.3, lab 7.3); (4) IEC 62443 risk assessment (lab 7.4). The HTML reports produced by NRJXpert (Report… button) are the deliverables.

Marking scheme of the level 6 synthesis project (out of 20)

CriterionPoints
Diagnosis and NRJXpert model of the feeder (load flow, hosting capacity)3
IEC 62559 use case sheets and SGAM mapping4
Studies: reliability (2, 4, 6 switches), IVVC, VPP, islanding — interpretation of the results5
Specification: interoperability (CIM, IEC 61850, points list), cybersecurity3
Bid analysis (TCO, grid) and FAT/SAT acceptance plan3
Quality of the report and of the presentation2
↑ Back to top

👩‍🏫4. Assessment and marking schemes

Lab report (out of 20)

CriterionPoints
Data and assumptions clearly stated (units, sources)3
Detailed hand calculation of at least one result5
Software results correctly recorded (screenshots, tables)4
Comparison and explanation of the differences4
Physical interpretation, answers to the « what happens if… » questions3
Presentation1

Sizing report (out of 20)

CriterionPoints
Realistic and justified load assessment3
Sizing of the generator, storage and electronics (method and rounding)5
Wiring: cross-sections, protection, voltage drops, costs4
Economic study (discounted cost, LCOE, comparison of variants)4
Sensitivity and reasoned recommendation3
Design note following the template (case studies)1

The end-of-level quizzes (8 to 12 questions) lend themselves to formative assessment: the student does them alone, the score is displayed; they can be reused for summative assessment on paper.

↑ Back to top

📐5. Exam subjects (2 h, documents allowed: formula sheet of the appendices)

Subject A — Electrification of a health post (technician)

  1. Draw up the energy balance of a health post (list of appliances provided).
  2. Size the array, battery, charge controller and inverter at 24 V for a worst month of 4.8 kWh/m²/d.
  3. Choose the cross-section of the array → controller cable (12 m, ΔU ≤ 3 %) and its protection.
  4. Calculate the annuity and the cost of the kWh over 15 years at 8 %.

Solution: follow example 3.3 and example 3.4; marks 5 + 7 + 4 + 4.

Subject B — Distribution network (engineer)

  1. Three-node network (data of lab 3): write Ybus in pu (base 10 MVA, 30 kV); do one Gauss-Seidel iteration.
  2. Comment on the NRJXpert results provided (Newton-Raphson): losses, reactive power of the PV node.
  3. Three-phase and phase-to-earth short circuit at node 3 (data provided), choice of the breaking capacity.
  4. A 2 MW PV plant is added at node 3: expected effects on the voltage and the losses; control law to propose.

Solution: examples 2.3, 2.4; lab 3; § 5.2. Marks 6 + 4 + 6 + 4.

Subject C — Hybrid project (master)

Compare for a 100 kW peak site: genset alone, PV + batteries, optimised hybrid (level 5 results provided). Discuss the discount rate, the price of diesel and the renewable share; conclude with a quantified recommendation.

↑ Back to top

🧩6. Final-year projects

  • Electrification plan of a municipality: centralised, decentralised, grid extension (case studies 1 and 2, level 5).
  • PV hosting capacity of a real MV feeder (operator's data) and connection rules.
  • Stability of an island microgrid (Saloum islands) with grid-forming batteries.
  • Update of the equipment database with market prices and sensitivity study of the LCOE.
  • Measurement / simulation comparison on an existing PV installation of the school.
  • Loss audit of a real feeder with smart-meter data (level 7) and AMI business case.
↑ Back to top

👩‍🏫7. Teaching tips

  • Require the hand calculation before using the software; mark the explanation of the differences more than the value obtained.
  • Vary one input at a time and ask for a qualitative prediction before running the calculation again.
  • Use local data (site weather, supplier prices, measured consumption profiles): motivation and the quality of the discussions improve markedly.
  • Recall the limits of the models: transformer ratio not represented by the server, indicative prices, typical days.
  • Unit entry errors (mH/H, kV/V, kW/W) are the first cause of absurd results: have the orders of magnitude checked.
↑ Back to top

👤Author

LT
Prof. Lamine THIAW
Department of Electrical Engineering
École Supérieure Polytechnique
Cheikh Anta Diop University, Dakar
lamine.thiaw@ucad.edu.sn
lamine.thiaw@esp.sn